Mixed and undifferentiated filler losses (changeover, breakdown, stoppage, defects)

Setup and adjustmentsAvailabilityFilling

In short

It appears in fewer than 1 of every 100 lines studied.

When it appears, it takes on average about 57 % of the line's lost time. Reported by 1 of the 120 studies that could observe it (sparse evidence).

What happens

Losses attributed to the filler combine several distinct underlying origins reported together in the source data: product or format changeovers with their adjustment time, unplanned mechanical or electrical breakdowns requiring corrective maintenance, generic line stoppages whose cause is not specified, and defective units detected at the filling station. Because the primary study logs all of these under a single equipment or report heading, the physical mechanism varies event by event rather than following one consistent failure mode.

What is done about it

Standardize changeover procedures separately from corrective-maintenance work orders, and improve stop-code granularity in the SCADA/MES configuration so that setup, breakdown, line-stop and defect events on the filler are logged under distinct, consistently applied categories. This reclassification enables proper root-cause analysis and allows each loss type to be targeted with its own dedicated improvement action rather than a single generic fix.

Practical guidance written from engineering knowledge; it is not a statistical estimate.

1Probability and evidence

Pooled over all segments. A wide interval is a result: it states how much the evidence allows us to know.
Probability of presence
0.5% [0.1–1.4%]
Expected share of lost time
0.3% [0.1–0.8%]
Share of lost time when present
57% [45–67%]
Studies / units
120 / 162
Evidence grade
D

Grade D: 0 or 1 study; the estimate is driven by partial pooling and priors, and the wide interval is the result.

2Probability by segment

Partially pooled estimates for each industry segment.
  • Dairy products
    0.5% [0.1–2.0%]18 studies
  • Soft drinks, bottled water and juices
    0.6% [0.1–2.1%]44 studies
  • Brewing, wine and spirits
    0.5% [0.1–2.0%]16 studies
  • Bakery and pasta
    0.6% [0.1–2.3%]0 studies
  • Meat, poultry and seafood
    0.6% [0.1–2.2%]6 studies
  • Fruit and vegetable processing
    0.6% [0.1–2.3%]4 studies
  • Grain and oilseed milling
    0.6% [0.1–2.1%]6 studies
  • Sugar and confectionery
    0.6% [0.1–2.2%]3 studies
  • Snacks, coffee, tea and other foods
    0.6% [0.1–2.2%]6 studies
  • Animal feed and pet food
    0.6% [0.1–2.3%]4 studies
  • Food manufacturing (unspecified or mixed)
    0.6% [0.1–2.2%]13 studies

3Mechanism, SCADA signature and countermeasure

Engineering guidance that helps recognise and address the cause; it is not part of the statistical estimate.

Mechanism

Engineering guidance

Losses attributed to the filler combine several distinct underlying origins reported together in the source data: product or format changeovers with their adjustment time, unplanned mechanical or electrical breakdowns requiring corrective maintenance, generic line stoppages whose cause is not specified, and defective units detected at the filling station. Because the primary study logs all of these under a single equipment or report heading, the physical mechanism varies event by event rather than following one consistent failure mode.

How it looks in SCADA data

Engineering guidance

In SCADA/MES the filler tag shows alternating machine states such as changeover, fault/alarm and running, each with its own downtime counter, together with a reject or defect counter tied to the filling station; however the stop codes and state transitions are not consistently mapped to a single root cause, so the historian shows a heterogeneous mix of short and long stops and quality rejects under the same equipment identifier. This inconsistency itself is diagnostic of a cluster where classification granularity is insufficient at the source.

Countermeasure

Engineering guidance

Standardize changeover procedures separately from corrective-maintenance work orders, and improve stop-code granularity in the SCADA/MES configuration so that setup, breakdown, line-stop and defect events on the filler are logged under distinct, consistently applied categories. This reclassification enables proper root-cause analysis and allows each loss type to be targeted with its own dedicated improvement action rather than a single generic fix.

4Sources

Every extracted datum with its study, value and verbatim quote.
  1. Defect rate: 0.200 % · as reported: “Taxa de Defeitos em Serviços (SDR)”
    Show verbatim quote
    Verificou-se que de janeiro a outubro de 2005 o indicador Taxa de Defeitos em Serviços (SDR) da empresa Gama S.A. teve a enchedora de partes sólidas Klockner colaborando em média 0,2 % e um pico de 1,02% conforme Figura 44.
  2. Lost time: 22.0 h · as reported: “Paradas de linha”
    Show verbatim quote
    Nesta análise de definição do problema verificou-se também que de janeiro a outubro de 2005 esta sala de produção teve em média 22 horas de paradas de linha conforme mostrado na Figura 46.
  3. Lost time: 162 min · as reported: “Setup (segunda-feira)”
    Show verbatim quote
    A Figura 60 mostra o valor do setup atual da klockner após os vários exercícios de SMED, onde ele foi reduzido em 70% nas segundas-feiras , saindo dos valores de 162 minutos para apenas 47 minutos.
  4. Lost time: 3.70 h · as reported: “Quebras da máquina (manutenção corretiva)”
    Show verbatim quote
    Para o indicador de Quebras na máquina Klockner, conforme a Figura 69, podemos ver que os tempos gasto em manutenção devido a quebra do equipamento foi reduzida de 6,9h para 3,7 horas o que representou uma melhora de 46% neste equipamento
  5. Lost time: 10.0 h · as reported: “Paradas de linha e setups”
    Show verbatim quote
    O indicador de paradas de linhas e setups da Klocner, conforme a Figura 70, teve uma redução de 23h de paradas e set ups para um tempo de 10 horas o que representou uma melhora de 57%.
  6. Lost time: 47.0 min · as reported: “Setup (segunda-feira)”
    Show verbatim quote
    A Figura 60 mostra o valor do setup atual da klockner após os vários exercícios de SMED, onde ele foi reduzido em 70% nas segundas-feiras , saindo dos valores de 162 minutos para apenas 47 minutos.
  7. Share of lost time: 70.0 % · as reported: “Máquina enchedora (problemas no equipamento Klockner)”
    Show verbatim quote
    observou-se, Figura 50, que 70% das paradas de linha estavam relacionadas a problemas no equipamento da Klockner, 16% por problemas de fornecimento de energia e 9% por problemas na máquina de injetora de tinta que faz as identificações nas bolsas plásticas.