Power supply disruption
In short
It appears in about 1 of every 100 lines studied.
When it appears, it takes on average about 57 % of the line's lost time. Reported by 2 of the 127 studies that could observe it (limited evidence).
What happens
An external voltage sag, outage or unstable grid supply interrupts electrical power to the line, causing drives, controllers and auxiliary equipment to lose function until power is restored. The stop originates outside the process itself, in the facility or utility electrical network rather than in a mechanical or process failure.
What is done about it
Install backup power sources such as UPS or standby generators for critical control and process equipment, and work with the utility or facility electrical team to monitor and improve supply quality. Implement surge protection, automatic transfer switches and a documented restart procedure to minimise downtime after power events.
Practical guidance written from engineering knowledge; it is not a statistical estimate.
1Probability and evidence
- Probability of presence
- 0.7% [0.2–1.9%]
- Expected share of lost time
- 0.4% [0.1–1.1%]
- Share of lost time when present
- 57% [46–68%]
- Studies / units
- 127 / 161
- Evidence grade
- C
Grade C: 2 to 4 studies, or an interval wider than 0.35.
2Probability by segment
- Dairy products0.8% [0.1–2.8%]13 studies
- Soft drinks, bottled water and juices1.0% [0.2–3.1%]26 studies
- Brewing, wine and spirits0.8% [0.1–2.8%]11 studies
- Bakery and pasta1.0% [0.2–3.4%]24 studies
- Meat, poultry and seafood0.8% [0.1–2.9%]9 studies
- Fruit and vegetable processing0.8% [0.1–3.0%]7 studies
- Grain and oilseed milling0.8% [0.1–2.8%]6 studies
- Sugar and confectionery0.8% [0.1–3.0%]9 studies
- Snacks, coffee, tea and other foods0.8% [0.1–2.7%]5 studies
- Animal feed and pet food0.8% [0.1–2.9%]7 studies
- Food manufacturing (unspecified or mixed)0.8% [0.1–2.9%]10 studies
3Mechanism, SCADA signature and countermeasure
Mechanism
Engineering guidanceAn external voltage sag, outage or unstable grid supply interrupts electrical power to the line, causing drives, controllers and auxiliary equipment to lose function until power is restored. The stop originates outside the process itself, in the facility or utility electrical network rather than in a mechanical or process failure.
How it looks in SCADA data
Engineering guidanceSCADA shows a simultaneous loss-of-communication or fault state across multiple independent machines on the same electrical feed, often with power-quality alarms, UPS switchover events or voltage/frequency deviation logs preceding the stoppage. All line equipment transitions to a stopped or fault state at the same timestamp rather than a single machine failing first.
Countermeasure
Engineering guidanceInstall backup power sources such as UPS or standby generators for critical control and process equipment, and work with the utility or facility electrical team to monitor and improve supply quality. Implement surge protection, automatic transfer switches and a documented restart procedure to minimise downtime after power events.
4Sources
- Share of loss events: 16.0 % · as reported: “Power supply problems”
Show verbatim quote
70% das paradas de linha estavam relacionadas a problemas no equipamento da Klockner, 16% por problemas de fornecimento de energia e 9% por problemas na máquina de injetora de tinta
- Lost time: 419 h · as reported: “disruptions in external power supply or failures in specific equipment units”
Show verbatim quote
At the same time, an additional 419 hours of unplanned downtime were recorded due to disruptions in external power supply or failures in specific equipment units
- Waste Management and Operational Efficiency Improvement in Cake and Pastry Factory Through Adapting DMAIC Methodology (2026)Open sourceMean event duration: 914 min · as reported: “Power Interruption”
Show verbatim quote
The Power Interruption category only happened twice; it had a high MTTR of 913.5 minutes, which brought the reliability down to 79.22%.