Automation and instrumentation failure
In short
It appears in about 1 of every 100 lines studied.
When it appears, it takes on average about 56 % of the line's lost time. Reported by 2 of the 127 studies that could observe it (limited evidence).
What happens
A fault develops in the control or instrumentation layer of the line, such as a PLC or drive malfunction, a failed sensor or transmitter, a damaged cable or connector, or corrupted control logic. Because equipment control, interlocks or measurement depend on these elements, the affected machine or section loses proper function and cannot continue running safely or correctly until the fault is diagnosed and repaired.
What is done about it
Apply preventive calibration, testing and cleaning of sensors, transmitters and control cabinets on a scheduled basis, keep spare I/O cards, drives and critical instruments on hand, and use condition monitoring or diagnostic alarms on control networks to detect degradation before a hard failure occurs. Where the loop is critical to production continuity, add redundancy or voting logic to tolerate a single instrument or module failure.
Practical guidance written from engineering knowledge; it is not a statistical estimate.
1Probability and evidence
- Probability of presence
- 0.8% [0.2–2.0%]
- Expected share of lost time
- 0.4% [0.1–1.1%]
- Share of lost time when present
- 56% [45–66%]
- Studies / units
- 127 / 161
- Evidence grade
- C
Grade C: 2 to 4 studies, or an interval wider than 0.35.
2Probability by segment
- Dairy products0.9% [0.1–3.0%]13 studies
- Soft drinks, bottled water and juices0.8% [0.1–2.4%]26 studies
- Brewing, wine and spirits0.9% [0.1–3.0%]11 studies
- Bakery and pasta1.1% [0.2–3.5%]24 studies
- Meat, poultry and seafood0.9% [0.1–3.1%]9 studies
- Fruit and vegetable processing0.9% [0.1–3.0%]7 studies
- Grain and oilseed milling0.9% [0.1–3.2%]6 studies
- Sugar and confectionery1.3% [0.2–4.3%]9 studies
- Snacks, coffee, tea and other foods0.9% [0.1–3.0%]5 studies
- Animal feed and pet food0.9% [0.1–3.2%]7 studies
- Food manufacturing (unspecified or mixed)0.9% [0.1–3.0%]10 studies
3Mechanism, SCADA signature and countermeasure
Mechanism
Engineering guidanceA fault develops in the control or instrumentation layer of the line, such as a PLC or drive malfunction, a failed sensor or transmitter, a damaged cable or connector, or corrupted control logic. Because equipment control, interlocks or measurement depend on these elements, the affected machine or section loses proper function and cannot continue running safely or correctly until the fault is diagnosed and repaired.
How it looks in SCADA data
Engineering guidanceThe event appears as a controller or instrumentation fault alarm, loss of communication between the PLC and field devices, frozen or out-of-range sensor readings, or an unexpected drive trip, all logged against an automation or instrumentation downtime reason code. Equipment state transitions to fault or stopped, and upstream or downstream machines may show starvation or blocking while the affected station is down for repair.
Countermeasure
Engineering guidanceApply preventive calibration, testing and cleaning of sensors, transmitters and control cabinets on a scheduled basis, keep spare I/O cards, drives and critical instruments on hand, and use condition monitoring or diagnostic alarms on control networks to detect degradation before a hard failure occurs. Where the loop is critical to production continuity, add redundancy or voting logic to tolerate a single instrument or module failure.
4Sources
- Lost time: 2.00 min · as reported: “Instruções ao operador B”
Show verbatim quote
9 Instruções ao operador B 2 0
- Lost time: 0 min · as reported: “Instruções ao operador B”
Show verbatim quote
9 Instruções ao operador B 2 0
- Strategic formulation of industrial maintenance based on equipment reliability in a sugar and ethanol production plant (2020)Open sourceTime between events: 6.18 log(min) · as reported: “Maintenance Instrumentation”
Show verbatim quote
Maintenance Instrumentation 15 6.178 (5.289; 7.067)
- Strategic formulation of industrial maintenance based on equipment reliability in a sugar and ethanol production plant (2020)Open sourceTime between events: 6.24 log(min) · as reported: “Maintenance Industrial Automation”
Show verbatim quote
Maintenance Industrial Automation 9 6.242 (5.095; 7.390)
- Strategic formulation of industrial maintenance based on equipment reliability in a sugar and ethanol production plant (2020)Open sourceNumber of events: 9.00 events · as reported: “Maintenance Industrial Automation”
Show verbatim quote
Maintenance Industrial Automation 9 6.242 (5.095; 7.390)
- Strategic formulation of industrial maintenance based on equipment reliability in a sugar and ethanol production plant (2020)Open sourceNumber of events: 15.0 events · as reported: “Maintenance Instrumentation”
Show verbatim quote
Maintenance Instrumentation 15 6.178 (5.289; 7.067)
- ESTRATÉGIA DE MANUTENÇÃO EM UMA USINA DE AÇUCAR E ALCOOL UTILIZANDO MODELO ESTATÍSTICO DE CONFIABILIDADE (2024)Open sourceNumber of events: 50.0 events · as reported: “Instrumentation (INST)”
Show verbatim quote
INST 50 47,83 51,52 2653,99 30,00
- ESTRATÉGIA DE MANUTENÇÃO EM UMA USINA DE AÇUCAR E ALCOOL UTILIZANDO MODELO ESTATÍSTICO DE CONFIABILIDADE (2024)Open sourceMean event duration: 47.8 min · as reported: “Instrumentation (INST)”
Show verbatim quote
INST 50 47,83 51,52 2653,99 30,00
- Reliability-Centered Maintenance Model to Improve OEE in a Mass-Consumption Food Company: A Case Study from Peru (2025)Open sourceShare of lost time: 19.0 % · as reported: “instrumentation faults”
Show verbatim quote
These reasons were linked to specific root causes: mechanical and electrical failures explained 30.2% of the stoppages, while instrumentation faults represented 19%.